PQube®

Power Standards Lab

C.N. Rood - Brussels (Belgium)

Building Entrance
setup v8


 
Meters

MeterValue
L1-N235,6V
L2-N235,3V
L3-N234,6V
N-E1,3V
L1-L2407,4V
L2-L3407,7V
L3-L1407,0V
L1 Amp5,362A
L2 Amp7,032A
L3 Amp17,796A
N Amp14,249A
Frequency49,974Hz
Voltage THDMax1,30%
L11,20%
L21,30%
L31,30%
THD-AMax54,50%
L141,90%
L254,50%
L314,90%
L1 FlickerPinst0,00
PST0,04
PLT0,13
L2 FlickerPinst0,00
PST0,06
PLT0,13
L3 FlickerPinst0,00
PST0,05
PLT0,13
IEC Zero Sequence V0,20%
IEC Negative Sequence V0,00%
IEC Zero Sequence I47,50%
IEC Negative Sequence I44,80%
L1-N Voltage Fundamental235,6V0deg
L2-N Voltage Fundamental235,2V-120deg
L3-N Voltage Fundamental234,6V120deg
L1 Current Fundamental4,928A34deg
L2 Current Fundamental6,145A-100deg
L3 Current Fundamental17,611A122deg
User Counter
(since 2015/02/03)
0
 
Energy

MeterValue
PowerTotal6,46kW
L10,96kW
L21,37kW
L34,13kW
Apparent PowerTotal7,10kVA
L11,27kVA
L21,65kVA
L34,18kVA
Reactive PowerTotal2,95kVAR
L10,83kVAR
L20,93kVAR
L30,63kVAR
True Power FactorTotal0,91
L10,76
L20,83
L30,99
Energy
(since 2015/02/03)
91,069MWh
Apparent Energy
(since 2015/02/03)
113,684MVAh
Reactive Energy
(since 2015/02/03)
63,683MVARh
Carbon
(since 2015/02/03)
29,516Mg
Carbon Rate2,09kg/h
Peak RMS Current
(since 2015/02/03)
1 cycle129,996Arms
1 minute37,922Arms
15 minute37,077Arms
Peak Power
(since 2015/02/03)
1 cycle31,99kW
1 minute16,82kW
15 minute14,58kW
Peak Apparent Power
(since 2015/02/03)
1 cycle46,03kVA
1 minute17,21kVA
15 minute15,08kVA
 
Harmonic H3

MeterValue
L1 Harmonic H30,5V113deg
1,402A196deg
L2 Harmonic H30,3V74deg
2,062A177deg
L3 Harmonic H30,4V155deg
1,258A270deg
 
Present Harmonic of Interest: 3
 
Internal Sensors

MeterValue
Battery voltage3,69V
Battery current0,02A
Battery cycles
(since 2012/09/11)
77
Status48
PQube Memory Usage73%
 

Data from the PSL PQube® by www.PowerStandards.com